2Flow DirectionThe flow through the 100-01 Hytrol Valve can be in one of twodirections. When flow is “up-and-over the seat,” it is in “normal”flow and

Strona 3

Diaphragm Check (#1 )1. Shut off pressure to the Hytrol Valve by slowly closing upstreamand downstream isolation valves. SEE CAUTION.2. Disconnect or

Strona 4

Maintenance Preventative MaintenanceThe Cla-Val Co. Model 100-01 Hytrol Valve requires no lubrication orpacking and a minimum of maintenance. However,

Strona 5

Lime DepositsOne of the easiest ways to remove lime deposits from the valvestem or other metal parts is to dip them in a 5-percent muriaticacid soluti

Strona 6

15810141661779OUTLETINLETGLOBE PATTERN9262712151416INLETOUTLETANGLE PATTERN222313 12 14 10 11 15 23TOP VIEW8" - 24" SEAT DETAIL1 1/4" -

Strona 7

100-01Hytrol Valve Service Data MODELINSTALLATION / OPERATION / MAINTENANCEDescription 100-01 Hytrol ValveThe CIa-VaI Model 100-01 Hytrol Valve is a m

Strona 8

COVER PIPE PLUG COVER BEARING SPRING STEM NUT DIAPHRAGM WASHER DISC RETAINER BODY *SPACER WASHERS DISC GUIDE SEAT PIPE PLUG STEM SEAT O-RING STUD 8&qu

Strona 9 - Hytrol Valve

UNDERSTANDING THE 600 SERIES VALVESIn 1987, Cla-Val introduced the Model 100-20 Hytrol as the basicmain valve for the 600 Series of automatic control

Strona 10 - Recommended Tools

CLA-VAL Copyright Cla-Val 2009 Printed in USA Specifications subject to change without notice. P.O. Box 1325 • Newport Beach, CA 92659-03

Strona 11 - STEM TRAVEL

INTRODUCTIONThe Cla-Val Model CDS6 Altitude Control is a spring loaded, 3-way,diaphragm-actuated control that provides high-level shut-off for Cla-Val

Strona 12 - Maintenance

This page was intentionally left blank!

Strona 13 - Inspection of Parts

SERVICE SUGGESTIONSUPPER (SPRING) SECTIONSYMPTOM PROBABLE CAUSE REMEDYVent leaks in Diaphragm (14) damaged Replace diaphragmlower cover (17) Diaph

Strona 14 - PARTS LIST

Altitude Pilot ControlTABLE 1TABLE 2 (SPRING ADJUSTMENT1 TURN = 0.0625”CDS6ACLA-VAL Copyright Cla-Val 2009 Printed in USA

Strona 15 - Hytrol Valve Service Data

This page was intentionally left blank!

Strona 18 -

Valve Position Indicator& Pilot System ComponentsWhen Ordering, Please Specify1. Valve Size2. Catalog No. X1013. Valve Series No. (Appears on Valv

Strona 19 - ALTITUDE CONTROL

PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 CLA-VAL CLA-VAL CANADA CLA-VAL EUROPE 4687 Christie DriveBeamsville

Strona 20 - SERVICE SUGGESTIONS

Valve Position IndicatorX101When ordering parts,please specify:• All Nameplate data• Item Number• Description• Material• Part NumberCLA-VAL Cop

Strona 21 - Altitude Pilot Control

This page was intentionally left blank!

Strona 24

This page was intentionally left blank!

Strona 25 - & Pilot System Components

THREADED 3/8" 18 NPT(TYP. BOTH ENDS)ARestriction Pipe FittingX58AWhen ordering parts,please specify:• All Nameplate Data• Description •SizePart N

Strona 26 - CDS6 Altitude Control

This page was intentionally left blank!

Strona 28

This page was intentionally left blank!

Strona 29

CLA-VAL Copyright Cla-Val 2009 Printed in USA Specifications subject to change without notice. P.O. Box 1325 • Newport Beach, CA 92659-03

Strona 30

CLA-VAL Copyright Cla-Val 2009 Printed in USA Specifications subject to change without notice. P.O. Box 1325 • Newport Beach, CA 92659-03

Strona 31 - Restriction Pipe Fitting

CLA-VAL Copyright Cla-Val 2009 Printed in USA Specifications subject to change without notice. P.O. Box 1325 • Newport Beach, CA 92659-03

Strona 32

3/8" Flow ControlCV2.12MAXSTAMP PART NO. ONSMOOTH SURFACERESTRICTEDFLOW3/8 - 18 NPT1.84ADJUSTING STEM(TURN CLOCKWISE TOINCREASE RESTRICTION)17210

Strona 33

The strainer is designed for use in conjunction with a Cla-ValMain Valve, but can be installed in any piping system wherethere is a moving fluid strea

Strona 35 - Flow Check Control

This page was intentionally left blank!

Strona 36

CLA-VAL Copyright Cla-Val 2009 Printed in USA Specifications subject to change without notice. P.O. Box 1325 • Newport Beach, CA 92659-03

Strona 37 - Flow Control

This page was intentionally left blank!

Strona 38 - 3/8" Flow Control

ITEM DESCRIPTION MATERIAL1 Pipe Plug Steel2 Strainer Plug Brass3 Gasket Copper4 Screen SST5 Body Brass123453/8 NPT2.062.72SIZE STOCK NUMBER3/8 x 3/8 3

Strona 39 - Flow Clean Strainer

This page was intentionally left blank!

Strona 40

Cla-Val ProductIdentificationProper IdentificationFor ordering repair kits, replacement parts, or forinquiries concerning valve operation, it is impor

Strona 41

HOW TO ORDERBecause of the vast number of possible configurations andcombinations available, many valves and controls are notshown in published produc

Strona 42

Complete Replacement Diaphragm Assemblies for 100-01 and 100-20 Hytrol Main ValvesFor: Hytrol Main Valves with Ductile Iron, Bronze Trim Materials—125

Strona 43 - Strainer

Repair Kits for 100-04/100-23 Hy-Check Main ValvesFor: Hy-Check Main Valves—125/150 Pressure Class OnlyIncludes: Diaphragm, Disc and O-Rings and full

Strona 45 - How to Order

This page was intentionally left blank!

Strona 47 - REPAIR KITS

This page was intentionally left blank!

Strona 48 - (no bucking spring)

DescriptionThe CIa-VaI Model 100-01 Hytrol Valve is a main valve forCIa-VaI Automatic Control Valves. It is a hydraulically operated,diaphragm-actuate